KYN28-12 Armored Remove AC Metal-Enclosed Switchgear

KYN28A-12 armored removable metal-enclosed switchgear is suitable for 3.6-12kv three-phase Ac 50Hz power grids for receivingand distributing electrical energy, and for controlling, monitoring and protecting circuits., Can be used for single bus, single bus segmented system or double bus system. The switchgear complies with lEC298 “AC metal-enclosed switchgear and controequipment with a rated voltage from lkv to 52kv and below”, lEc694 “High Voltage switch and control Equipment sharing Terms”China’s GB3906 (3-35kv AC metalenclosed switchgear) and DlA04 “indoor Ordering conditions for Ac high-voltage switchgear “Germ an DIN.vDE0670” AC switching eguipment with a rated voltage above lky “and other standards. It also has perfect and reliable anti-misoperation functions.

Type designation

MODEL: KYN 28 – 12/ □ □ □ □
 
KArmored removable metal-enclosed switchgear
YRemovable
NConditions of use:(indoor)
28Design Number
12Rated voltage (kv)
□0ne-time plan number
□Operating mechanism characteristic code, D: electromagnetic; T spring
□Rated current(A)
□Rated short-circuit breakingcurrent (kA)

Environmental conditions

● Ambient air temperature: maximum temperature 40 ℃, minimum temperature – 15 ℃;
● Relative humidity: the daily average value is not more than 95%, the daily average water vapor pressure is not more than 2.2KPa, the monthly average value is not more than 90%, and the monthly average water vapor pressure is not more than 1.8KPa;
● Altitude: 1000m and below;
● Seismic intensity: no more than 8 degrees;
● The surrounding air shall not be obviously polluted by corrosive or combustible gas, water vapor, etc;
● Places without frequent violent vibration;
● In case of use under normal environmental conditions beyond those specified in GB3906, the user and the manufacturer shall negotiate.

Switch cabinet dimensions

enclosed switchgear Dimensional drawing
A. Busbar compartment9.Removable partition
B. Circuit breaker compartment10. Secondary plug
C. Cable compartment11. Auxiliary switch
D. Meter compartment12. Moving curtain
1.shell13. Withdrawable handcart
1.1 Pressure release plate14. Grounding knife operating mechanism
1.2 Control cable cover15. Cable Seal Terminal
2.Branch bus16. Base plate
3. Bus17. Lead screw mechanism
4. Static contact device18. Grounded main bus
5. Spring contacts19. Attachable horizontal partition
6. Grounding knife 
7. Current transformer 
8. Voltage transformer 

Main technical parameter

BrandZHENGXI
ModelKYN
Rated Voltage24KV
Rated Frequency50Hz
Breaker Rated Current630A 1250A 1600A 2000A 2500A 3150A
Switchgear Rated Current630A 1250A 1600A 2000A 2500A 3150A
Rated Short-Time Withstand Current (4S)16KA 20KA 25KA 31.5KA 40KA 50KA
Rated Peak Withstand Current (Peak)40KA 50KA 63KA 80KA 100KA 125KA
High Voltage Backup Fuse Breaking Current16KA 20KA 25KA 31.5KA 40KA 50KA
Rated Short-Circuit Closing Current (Peak)40KA 50KA 63KA 80KA 100KA 125KA
Rated Insulation Level1Min Powerfrequencywithstandvoltage24KV 32KV42KV
Lightningimpulsewithstandvoltage40KV 60KV75KV
Protection LeveEnclosureis lP4X,isolation room, breaker room door is IP2X

Note: Short circuit capacity of current transformer is considered separately