When selecting a variable frequency drive (VFD), motor power is only part of the picture. A 15 kW centrifugal pump and a 15 kW conveyor may use motors with the same rated power, but their torque and overload requirements can be very different.
The key is understanding whether the machine is a constant torque or variable torque load.
This guide explains the difference, common applications, and what to check when selecting a VFD.

A constant torque load requires approximately the same torque across its normal speed range.
For example, slowing down a loaded conveyor does not remove the weight or friction the motor must overcome. The motor may still need substantial torque at low speed.
Typical applications include:
These applications often require good starting torque and higher short-term overload capability.
With a variable torque load, the required torque decreases as speed decreases.
The most common examples are centrifugal pumps and fans.
Typical applications include:
Because the power requirement can fall rapidly as speed decreases, these applications often offer good opportunities for VFD energy savings.
| Feature | Constant Torque | Variable Torque |
|---|---|---|
| Torque at reduced speed | Remains relatively constant | Decreases |
| Typical applications | Conveyor, mixer, extruder | Pump, fan, blower |
| Starting torque | Often higher | Usually lower |
| Typical VFD duty | Heavy Duty | Normal Duty |
| Energy savings | Depends on process | Often significant at reduced speed |
These are general classifications. Actual VFD sizing should always be based on the motor and load requirements.
The difference becomes clearer when motor speed is reduced.
For a constant torque load:
Torque ≈ Constant
Power ∝ Speed
If speed is reduced to 80%, the mechanical power requirement is approximately 80%, assuming torque remains constant.
Centrifugal pumps and fans generally follow the Affinity Laws:
For example:
| Motor Speed | Approx. Theoretical Power |
|---|---|
| 100% | 100% |
| 90% | 72.9% |
| 80% | 51.2% |
| 70% | 34.3% |
| 50% | 12.5% |
This is why reducing the speed of a centrifugal pump or fan can significantly reduce energy consumption.
However, these figures are theoretical. Actual savings depend on the pump or fan curve, system resistance, static head, motor efficiency, VFD efficiency, and operating conditions.
The following table provides a quick way to identify common industrial loads:
| Application | Load Type | Main VFD Consideration |
|---|---|---|
| Centrifugal pump | Variable torque | Flow and pressure control |
| HVAC fan | Variable torque | Energy efficiency |
| Centrifugal blower | Variable torque | Speed and airflow control |
| Conveyor | Constant torque | Starting and overload torque |
| Extruder | Constant torque | Low-speed torque |
| Mixer | Often constant torque | Starting load |
| Screw feeder | Constant torque | Torque at low speed |
| Positive displacement pump | Constant torque | Pressure and load torque |
One important distinction is that not every pump is a variable torque load. Centrifugal pumps are typically variable torque, while positive displacement pumps generally behave more like constant torque loads.
Consider two 15 kW motors:
Application A: 15 kW centrifugal pump
The drive mainly needs to control flow or pressure and usually operates without frequent high overloads. A suitable Normal Duty (ND) VFD may be sufficient if its continuous output current meets the motor requirements.
Application B: 15 kW loaded conveyor
The conveyor may need to start under load, provide high torque at low speed, and withstand temporary overloads. A Heavy Duty (HD) VFD may therefore be more appropriate.
So even though both motors are 15 kW, the correct VFD selection may not be identical.

The key lesson is:
Do not select a VFD by motor kW alone. Check the motor rated current and actual load requirements.
Many VFD manufacturers provide both Normal Duty and Heavy Duty ratings.
Normal Duty is commonly used for variable torque applications such as:
These applications generally require less short-term overload capability.
Heavy Duty is commonly used for constant torque applications such as:
These loads may require higher starting torque or greater overload capacity.
Some VFD families, for example, may specify overload levels around 110% for Normal Duty and 150% for Heavy Duty for a defined period.
However, these numbers are not universal. Overload current and duration vary by VFD manufacturer and model.
Always check the specific datasheet for:
For most industrial applications, start with these six factors:
Check the motor nameplate.
The VFD’s continuous output current should meet the motor requirements. Do not rely only on kW or HP.
Determine whether the machine is:
Constant torque: conveyor, extruder, mixer, screw feeder
or
Variable torque: centrifugal pump, fan, blower
Ask whether the machine starts loaded and whether temporary load peaks are expected.
A loaded conveyor generally requires more attention to overload capacity than a centrifugal fan.
Constant torque operation at very low speed can create a motor cooling problem because the motor’s shaft-mounted fan also slows down.
For continuous low-speed, high-torque operation, forced ventilation or an inverter-duty motor may be required.
High-inertia loads may need longer acceleration or deceleration times.
Applications requiring rapid stopping may also need a braking resistor, braking unit, or regenerative solution.
Check whether the application requires:
The appropriate control method depends on the required torque, speed accuracy, and process control.
Two motors with the same kW rating can have different rated currents and load characteristics.
Use the motor nameplate current plus the load profile when selecting a VFD.
Centrifugal pumps are generally variable torque loads, but positive displacement pumps are not.
Always identify the actual pump type.
Running a motor slowly does not necessarily mean it is lightly loaded.
A conveyor may operate at low speed while still requiring high torque. If this continues for long periods, additional motor cooling may be necessary.
Instead of simply asking:
“Please quote a 15 kW VFD.”
provide:
For example:
15 kW, 380 V three-phase motor, rated current XX A, driving a loaded belt conveyor, operating from 20–50 Hz.
This gives the supplier much more useful information for selecting the correct drive.
ZHENGXI manufactures variable frequency drives for industrial motor control applications including pumps, fans, conveyors, and production machinery. For OEM or project selection, the final VFD model should be confirmed against the actual motor nameplate and operating conditions.

Yes, provided the VFD’s current rating, overload capacity, control method, and operating conditions meet the application requirements.
A drive may have different allowable motor ratings under Normal Duty and Heavy Duty operation, so check the manufacturer’s datasheet.
Conveyors are generally considered constant torque loads, but actual torque depends on belt design, friction, inclination, material weight, and whether the conveyor starts loaded.
For heavily loaded conveyors, starting torque should be evaluated separately.
Variable torque applications such as centrifugal pumps and fans often offer greater energy-saving potential when operating below full speed because their power requirement decreases rapidly with speed.
Actual savings still depend on the complete system and operating profile.
The main difference between constant torque and variable torque loads is how the required torque changes with motor speed.
Centrifugal pumps and fans are typically variable torque loads and are commonly matched with Normal Duty VFD ratings.
Conveyors, extruders, and mixers are commonly constant torque loads and may require Heavy Duty ratings with greater overload capability.
When selecting a VFD, focus on four key factors:
motor rated current + load type + overload requirement + operating speed range.
Motor kW or HP is only the starting point.